Add to Cart
1. Product Description
1600 series intelligent electro-pneumatic valve positioner is easy to operate and has rich software functions. It can easily be operated via the LCD and keypad.
The product is designed for integral pneumatic control valve, particularly suitable for angle seat valves and diaphragm valves.
Through detecting the position sensor signal, the positioner adjusts the valve position quickly and accurately.
2.Technical Datas
Material | PC,PA6-GF30,Stainless Steel,SI |
Power supply | 24V DC ±10% |
Set-point signal | 0/4-20mA or 0-5/10 V |
Input resistance for set-point signal | 240Ω at 0/4-20mA, 21KΩ at 0-5/10V |
Control medium Dust concentration Particle density Pressure condensation point Oil concentration | Neutral gases, air DIN ISO 8573-1 Class 5 (<40μm particle size) Class 5 (<10mg/m3) Cass 3 (<-20°C) Class 5 (<25mg/m3) |
Ambient Temperature | 0-70°C |
Pneumatic Connection | Plug-in hose connector G1/4(internal Φ6mm) |
Electrical Connection | M12 3-pins B-coded(cable ø 4-6mm) M12 4-pins D-coded(cable ø 4-6mm) M12 5-pins A-coded(cable ø 4-6mm) |
Supply Pressure | 3~7 bar, specific values depending on the actuator |
Air Flow Rate | 17 L/min, 58 L/min(only single-acting) |
Stroke Control Range | Linear 5-50mm Rotary 90° |
Installation | As required, Preferably with actuator in upright position, Screw. |
Protection Class | IP65 |
Power Consumption | <5W |
Explosion Proof | Ex nA IIC T4 |
3. Product type selection
4. Dimensions
5. Schematic diagram
6. Electrical connections and pneumatic connections
X1 | ||
---|---|---|
Pin | Description | Signal type |
1 | Analogue signal output + | 0/4 – 20 mA or 0 – 5/10 V |
2 | Binary signal output 1 | 0/24 V |
3 | Binary signal output 2 | 0/24 V |
4 | Binary signal input + | 0-3V =“0”, 15-30V =“1” |
5 | Signal common GND | GND |
X2(Optional for process control only) | ||
---|---|---|
Pin | Description | Signal type |
1 | Transmitter input + | +24 V |
2 | Transmitter signal output | 4 - 20mA |
3 | Transmitter GND | GND |
X3 | ||
---|---|---|
Pin | Description | Signal type |
1 | Power supply + | +24 V |
2 | Power supply GND | GND |
3 | Set signal input + | 0/4 – 20 mA or 0 – 5/10 V |
4 | Set signal input GND | GND |
P | Air supply enter (built-in filter, filter size 5 μm) |
R | Air exhaust |
C | Check valve |
A1 | Pilot air outlet 1 |
A2 | Pilot air outlet 2 |